EBG HomeProductsServiceSystem IntegrationCustomer ProfileFeedbackContact UsOnline Enquiry



  Power Control Centre

      Technical Specification
      Constructional Features
      Compartmentalised Design
      Cable Alley

      Busbar System

  Motor Control Centre

  Intelligent Electronic Devices
  Allied Equipment
Tips for PCC type TF
Tips for MCC type TQ
FAQs
Click Here For Online Seminar/Demo Request


 
    

 Technical Specification


    Rated Service Voltage : 415 V
    Rated Frequency : 50h
    Rated Insulation Voltage : 660 V
    Busbar System : TP-E or TPN-E   (with isolable neutral)
    Max.Rating Of Busbars : 4000 A
    Fault Level Withstand : 70 kA FOR 1 SEC
    Degree Of Protection : IP54 AS PER IS-2147

Higher rating of busbar, frequency - 60Hz, higher fault levels available on request