Regular maintenance helps
ACB Removal


  • Trip the ACB. Isolate all remote voltage sources. ENSURE THAT CONTROL CIRCUIT IS DE-ENERGISED.
  • Rack out the ACB to ‘Isolated’ position. Open compartment door. Pull out the ACB to ‘Maintenance’ position.
  • Position the ACB lifting truck in front of ACB. Put lifting sling around the ACB lifting lugs.
  • Remove nuts anchoring ACB to telescopic rails and lift the ACB carefully by raising lifting arm of ACB lifting truck.
  • Push the rails inside and close the compartment door.
  • After removal, the ACB should be stored properly. Keep it covered with a polythene bag, free from dust.
  • While re-inserting the ACB, ensure that the ACB as well as all downstream feeder switches/isolators are open.

     