1. Always use copper wires/cables for control purposes.
2. Inter-unit wiring within the same panel is through the wireway on the right hand side.
3. Intersection wiring is through the horizontal wireway at the top along. With the auxiliary bus.
4. In the single front version, rear access to the vertical wireway is available if the section is installed at least one metre away from the wall.
5. For double front sections, inter-front wiring is through the shield in the middle of the section.
6. Refer to the relevant scheme diagrams and terminal charts for inter-connections.
7. Special connectors are provided in cable alley, auxiliary bus zone for communication cables, wherever required. These cables are run in front vertical pillar, providing a shield from other cables in cable alley.
8. Shielding on communication cables should not be earthed in the MCC.