Regular maintenance helps
Routine checks


  • Check tightness of bolted joints

    Prior to energisation

    Six months after load is connected

    One year after the second check and then once a year.

  • THIS IS VERY IMPORTANT FOR ALUMINIUM BUSBARS AND LINKS.

  • Inspect all wiring for wear and cuts.

  • Look for indications of overheating, arcing or insulation breakdown.

  • Inspect main and arcing contacts. Replace all worn out contacts.

  • Inspect all auxiliary and control circuits for desired functioning.

  • Grease ACB parts and carry out maintenance as per ACB Instruction Manual.

  • Grease racking screw and telescopic rails at least once a year. Use grease “HP-LETHON-2” OR “SYNTHOLUBE-20 of HJ Leach & Co.”

  • Inspect all door gaskets for wear. Replace where necessary.

  • Keep the switchboard free of dust. Use vacuum cleaner to remove the dust.

     