Regular maintenance helps
ACB Removal


  • Trip the ACB. Isolate all remote voltage sources. ENSURE THAT CONTROL CIRCUIT IS DE-ENERGISED.

  • Rack out the ACB to ISOLATED POSITION. Open compartment door. Pull out the ACB to maintenance position.

  • Position the ACB lifting truck in front of ACB. Put lifting sling around the ACB lifting lugs.

  • Remove nuts anchoring ACB to telescopic rails and lift the ACB carefully by raising lifting truck.

  • Push the rails inside and close the compartment door.

  • After removal, the ACB should be stored properly. Keep it covered with a polythene bag, free from dust.

  • While re-inserting the ACB, ensure that the ACB as well as all downstream feeder switches/isolators are open.

     